    • Hubei Dayu Hanguang Vacuum Electric Co.,Ltd.
      CN EN

      Vacuum interrupter for 12kV-40.5kV outdoor VCB

      Model:VITD12/1250-25

      Category:Vacuum interrupter


      Product details

      TD314B戶外斷路器用真空滅弧室結構圖
      Main Technical Specification
      VOLTAGE RATINGS
      Rated voltage(Ur) kV 12
      Rated short-time(1min)power-frequency withstand voltage(Ud) kV 48
      Rated lightning impulse withstand voltage(Peak)(Up) kV 85
      Rated frequency(fr) Hz 50
      CURRENT RATINGS
      Rated current(Ir) A 1250
      Circuit resistance at lowest rated contact force μΩ ≤30
      Rated short-circuit breaking current(lsc) kA 20/25
      Breaking operations of rated short circuit breaking current Times 30
      Rated short-time withstand current(lk) kA 20/25
      Rated duration of short-circuit(tk) s 4
      Rated peak withstand current(lp) kA 50/63
      Rated short-circuit making current(lMc) kA 50/63
      Rated cable-charging breaking current(lc) A 25
      Rated breaking current of single capacitor bank(lsb) A 400/630
      Rated breaking current of back-to-back capacitor bank(lbb) A 400
      MECHANICAL DATA
      Weight of movable parts kg ≤0.7
      Closing force due to bellow and atmosphere N 70±40
      Force required to hold contacts open at full stroke N 120±50
      MECHANICAL REQUIREMENTS
      Clearance between open contacts mm 9±1
      Average opening speed (contact close position~75%contact gap) m/s 12±0.3
      Average closing speed (30%contact gap-contact close position) m/s 0.8±0.2
      Rated added external contact final force N 2000±200
      Added external contact force at contact touch point 1400±100
      Contact bouncing duration at closing operation ms ≤2
      Closing and opening non-simultaneity of three-phase contacts ms ≤1
      Maximum rebound during opening mm ≤2
      LIFE
      Storage life years 20
      Rated mechanical endurance Times 10000
      Contacts limit erosion mm 3